VEGA VEGAPULS 67 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART two-wire User Manual
Page 35
M
in. adjustment
0
.00 %
=
5
.000 m(d)
4.000
m(d)
3
P
repare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
4
E
nter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5
S
ave the settings with [OK] and move to "Max. adjustment" with [-
>
]
.
P
roceed as follows:
M
ax. adjustment
100
.00 %
=
1
.000 m(d)
2.000
m(d)
1
P
repare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
2
E
nter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.
3
S
ave the settings with [OK] and move to "Medium selection" with
[->]
.
E
ach product has different reflective properties. In solids, these are
dust generation, material cones and additional echoes caused by the
vessel wall. Due to the medium selection, the sensor is adapted in an
optimum way to the product and the accuracy, particularly for products
with bad reflective properties, is increased considerably.
M
edium
Bulk solid
W
ith solids, you can also choose between "Powder/Dust", "Granular/
Pellets" or "Ballast/Pebbels".
Carry out max. adjust-
ment
Medium selection
VEGAPULS
67 • 4 … 20
mA/HART two-wire
35
6 S
et up with the indicating and adjustment module PLICSCOM
32938
-EN
-100514