Fig. 21: Deviation VEGAFLEX 67 in cable version

1

Dead zone - no measurement possible in this area

L

Probe length

Influence of the ambient temperature to the sensor electronics
Temperature drift

0.03 %/10 K relating to the max. measuring range
or max. 0.3 %

Temperature drift - Digital output

3 mm/10 K relating to the max. measuring range or
max. 10 mm

Ambient conditions

Ambient, storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

Process conditions

Process pressure

-

Flange version ≤ 2"/DN 50

-0.5 … +16 bar/-50 … +1600 kPa (-7.3 … +232 psig),
depending on the process fitting

-

Flange version > 2"/DN 50

-0.2 … +16 bar/-20 … +1600 kPa (-2.9 … +232 psig),
depending on the process fitting

Process temperature (flange temperature)

-40 … +150 °C (-40 … +302 °F)

The measurement error from the process condi-
tions is in the specified pressure and temperature
range of below 1 %.