4 … 20
mA signal not stable
l
L
evel fluctuations
à Set the integration time via the indicating and adjustment
module or PACTware
l
no atmospheric pressure compensation
à Check the pressure compensation in the housing and clean
the filter element, if necessary
?
4 … 20
mA signal missing
l
W
rong connection to power supply
à Check connection according to chapter "Connection steps"
and if necessary, correct according to chapter "Wiring plan"
l
N
o power supply
à Check cables for breaks; repair if necessary
l
O
perating voltage too low or load resistance too high
à Check, adapt if necessary
?
C
urrent signal greater than 22 mA or less than 3.6 mA
l
electronics module or measuring cell defective
à Exchange instrument or return instrument for repair
I
n Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
?
E
013
l
no measured value available
8)
à Exchange instrument or return instrument for repair
?
E
017
l
A
djustment span too small
à repeat with modified values
?
E
036
l
no operable sensor software
à Carry out a software update or send the instrument for repair
?
E
041
l
H
ardware error
à Exchange instrument or return instrument for repair
D
epending on the failure reason and measures taken, the steps
described in chapter "Set up" must be carried out again, if necessary.
8)
F
ault message can also appear if the pressure is higher than the nominal
range.