VEGA VEGAFLEX 61 Profibus PA User Manual
Page 58
Status
code
Description according to Pro-
fibus standard
Possible cause
0x0C
bad - sensor failure
l Hardware error
l Converter error
l Leakage pulse error
l Trigger error
0x10
bad - sensor failure
l Measured value generation error
0x1f
bad - out of service constant
"O
ut of Service" mode switched on
0x44
uncertain - last unstable value
Failsafe replacement value (Failsafe-Mode = "Last value" and
already valid measured value since switching on)
0x48
uncertain substitute set
l Switch on simulation
l Failsafe replacement value (Failsafe-Mode = "Fsafe value")
0x4c
uncertain - initial value
Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)
0x51
uncertain - sensor; conversion
not accurate - low limited
Sensor value < lower limit
0x52
uncertain - sensor; conversion
not accurate - high limited
Sensor value > upper limit
0x80
good (non-cascade) - OK
OK
0x84
good (non-cascade) - active
block alarm
Static revision (FB, TB) changed (10 sec. active, after the parameter
of the static category was written)
0x89
good (non-cascade) - active ad-
visory alarm - low limited
Lo-Alarm
0x8a
good (non-cascade) - active ad-
visory alarm - high limited
Hi-Alarm
0x8d
good (non-cascade) - active cri-
tical alarm - low limited
Lo-Lo-Alarm
0x8e
good (non-cascade) - active cri-
tical alarm - high limited
Hi-Hi-Alarm
58
VEGAFLEX
61 • Profibus PA
10 Supplement