beautypg.com

3 exchange or shorten cable/rod – VEGA VEGAFLEX 61 Profibus PA User Manual

Page 39

background image

Status accor-
ding to NE 107

Error code

Text message

Cause/Rectification

E

017

Adjustment span too small

Adjustment not within the specifica-
tion. Carry out the adjustment again,
increasing the distance between
min. and max. adjustment

E

036

No operable software

Failed or interrupted software up-
date/Repeat software update

E

042

Hardware error, electronics defec-
tive

Exchange the instrument or send it
in for repair

E

043

Hardware error, electronics defec-
tive

Exchange the instrument or send it
in for repair

E

113

Communication conflict

Exchange the instrument or send it
in for repair

Depending on the failure reason and measures taken, the steps
described in chapter "Set up" must be carried out again, if necessary.

8.3 Exchange or shorten cable/rod

The cable or rod (meas. part) of the probe can be shortened, if
necessary. To loosen the meas. part you need two fork spanners with
spanner width 8.

1

Loosen the measuring component by applying a fork spanner to
the flat surfaces (SW 8), provide counterforce with another fork
spanner (SW 8)

2

Unscrew the loosened measuring component manually

3

Place the enclosed new double washer onto the thread.

Caution:
Make sure that the two components of the double washer remain
together.

4

Screw in a new measuring part manually

5

Exert counterforce with the second fork spanner and tighten the
measuring component on the flat surfaces with a torque of 7 Nm
(5.16 lbf ft).

Reaction after fault rec-
tification

Exchanging the cable/
rod

VEGAFLEX

61 • Profibus PA

39

8 Maintenance and fault rectification

31835

-

EN

-100426