beautypg.com

VEGA VEGAFLEX 61 Profibus PA User Manual

Page 14

background image

If possible, avoid sockets. Mount the sensor flush with the vessel top. If
this is not possible, use short sockets with small diameter.

Higher sockets or sockets with a bigger diameter can generally be
used. They simply increase the upper dead band. Check if this is
relevant for your measurement.

In such cases, always carry out a gating out of false signals after
installation. You can find further information under "Setup procedure".

h

d

d

h

DN40 ... DN150

£ 150

> DN150 ... DN200

£ 100

Fig. 6: Mounting socket

When welding the socket, make sure that the socket is flush to the
vessel wall.

1

2

Fig. 7: Socket must be installed flush
1

Unfavourable installation

2

Socket flush - optimum installation

Socket

14

VEGAFLEX

61 • Profibus PA

4 Mounting

31835

-EN

-100426