VEGA VEGACAP 62 - Relay (DPDT) User Manual
Page 31
31
9 Supplement
VEGACAP 62 • - Relay (DPDT)
30004-EN-130916
1
2
3
-50°C
(-58°F)
50°C
(122°F)
40°C
(104°F)
-40°C
(-40°F)
80°C
(176°F)
0°C
(32°F)
100°C
(212°F)
150°C
(302°F)
200°C
(392°F)
Fig. 33: Ambient temperature - Process temperature
1 Process temperature
2 Ambient temperature
3 Temperature range with temperature adapter
Dielectric constant
≥ 1.5
Electromechanical data
Cable entry/plug (dependent on the version)
Ʋ Single chamber housing
– 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind plug M20 x 1.5; attached 1 x cable entry
M20 x 1.5
or:
– 1 x cable entry ½ NPT, 1 x blind plug ½ NPT, 1 x cable
entry ½ NPT
or:
– 1 x plug M12 x 1; 1 x blind plug M20 x 1.5
Spring-loaded terminals
for wire cross-section up to 1.5 mm² (AWG 16)
Adjustment elements
Mode switch
Ʋ Min.
Min. detection or dry run protection
Ʋ Max.
Max. detection or overflow protection
DIL switch for measuring range selection
Ʋ range 1
0 … 20 pF
Ʋ range 2
0 … 85 pF
Ʋ range 3
0 … 450 pF
Potentiometer
Switching point adaptation
Voltage supply
Operating voltage
20 … 253 V AC, 50/60 Hz, 20 … 72 V DC (at
U >60 V DC, the ambient temperature can be max.
50 °C/122 °F)
Power consumption
1 … 8 VA (AC), approximately 1 W (DC)
Electrical protective measures
Protection rating
IP 66/IP 67