4 Mounting

VEGACAP 62 • - Relay (DPDT)

30004-EN-130916

The process fitting must be sealed if there is gauge or low pressure in

the vessel. Before use, check if the seal material is resistant against

the measured product and the process temperature.
The max. permissible pressure is specified in chapter "Technical

data" or on the type label of the sensor.

If condensate forms on the vessel top, the run-off liquid can cause

bridging and hence faulty switchings.
For this reason, use a screening tube or a longer insulation. The

length depends on the amount of condensate and the drain-off be-

haviour of the product.

4.2 Mounting instructions

Due to the effects of agitators, equipment vibration or similar, the level

switch can be subjected to strong lateral forces. For this reason, do

not use an overly long electrode for VEGACAP 62, but check if you

can mount a short level switch on the side of the vessel in horizontal

position.
Extreme vibration caused by the system, e.g. due to agitators or

turbulence in the vessel from fluidisation, can cause the probe of

VEGACAP 62 to vibrate in resonance. If a longer rod version is neces-

sary, you can secure the probe by fastening a suitable isolated brace

or guy directly above the end of the rod.

If the instrument is mounted in the filling stream, unwanted false

measurement signals can be generated. For this reason, mount the

instrument at a position in the vessel where no disturbances, e.g. from

filling openings, agitators, etc., can occur.
This applies particularly to instrument versions with a longer probe.

Fig. 5: Inflowing medium

Pressure/Vacuum

Condensation

Agitators and fluidization

Inflowing medium