VEGA VEGACAP 62 - Relay (DPDT) User Manual
Page 30
30
9 Supplement
VEGACAP 62 • - Relay (DPDT)
30004-EN-130916
Ʋ Max.
253 V AC, 253 V DC
With circuits > 150 V AC/DC, the relay contacts must be
in the same circuit.
Switching current
Ʋ Min.
10 µA
Ʋ Max.
3 A AC, 1 A DC
Breaking capacity
Ʋ Min.
50 mW
Ʋ Max.
750 VA AC, 54 W DC
If inductive loads or stronger currents are switched
through, the gold plating on the relay contact surface will
be permanently damaged. The contact is then no longer
suitable for switching low-level signal circuits.
Contact material (relay contacts)
AgNi (Au plated) or AgSnO (Au plated)
Modes (switchable)
Min./Max.
Switching delay
Ʋ When immersed
0.7 s
Ʋ When laid bare
0.7 s
Ʋ In case of failure
1 s
Ambient conditions
Ambient temperature on the housing
-40 … +80 °C (-40 … +176 °F)
Storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
Process conditions
Process pressure
Ʋ Standard
-1 … +64 bar/-100 … 6400 kPa (-14.5 … 928 psig)
Ʋ with screening tube adapter (PN1)
0 … +1 bar/0 … 100 kPa (0 … 14.5 psig)
Process temperature VEGACAP 62 of
316L
-50 … +150 °C (-58 … +302 °F)
Process temperature (thread or flange
temperature) with temperature adapter
(option)
-50 … +200 °C (-58 … +392 °F)