6 Setup

VEGACAP 65 • - Relay (DPDT)

30016-EN-130916

You can adapt the switching point to the solid with the potentiometer.

With the potentiometer (1) and the measuring range selection switch

(2) you can change the sensitivity of the probe to the electrical proper-

ties of the product and the conditions in the vessel. This is necessary

so that the level switch can also reliably detect products e.g. with very

low or very high dielectric figure.
range 1: 0 … 20 pF
Range 2: 0 … 85 pF
Range 3: 0 … 450 pF

With the mode switch (3) you can change the switching condition of

the relay. You can set the required mode (max. - max. detection or

overfill protection, min. - min. detection or dry run protection).
We recommend connecting according to the quiescent current princi-

ple (relay contact deenergizes when the switching point is reached),

because the relay always takes on the same (safe) condition if a

failure is detected.

Control lamp for indication of the switching status

green = relay energized

red = relay deenergized

red (flashing) = failure

The adjustment of the switching point is only possible in installed

condition.
The specifications in parenthesis refer to the preceding illustration.
Vertically mounted probes

1. Set mode switch (3) to mode max.
2. Set meas. range selection switch (2) to range 1.
3. Fill the vessel up to the requested level.
4. Turn potentiometer (1) to position 10.

When the control lamp (6) lights red: set the measuring range

selection switch (2) to the next higher measuring range.
When the control lamp (6) lights green: continue with the next

item.

5. Turn the potentiometer (1) very slowly anticlockwise until the

control lamp (6) lights red.

The measuring system is now ready for operation.
1. Set mode switch (3) to mode min.
2. Set meas. range selection switch (2) to range 1.
3. Lower the level to the requested min. level.
4. Turn the potentiometer (1) to 0, the control lamp (6) lights green.
5. Turn the potentiometer (1) very slowly clockwise until the control

lamp (6) lights red. If the control lamp does not light red, set the

meas. range selection switch (2) to the next higher stage and

Switching point adapta-

tion (1)

Measuring range selec-

tion switch (2)

Mode adjustment (3)

Signal lamp (6)

Switching point adjust-

ment

Mode max. (max. level

detection)

Mode min. (min. level

detection)