Electromechanical data - version IP 66/IP 68 (1 bar)
Cable entry
Ʋ Single chamber housing
1 x IP 68 cable gland M20 x 1.5; 1 x blind plug M20 x 1.5
Ʋ Double chamber housing
1␣x IP␣68 cable gland M20␣x␣1.5; 1␣x blind stopper
M20␣x␣1.5; 1␣x blind stopper M16␣x␣1.5
Connection cable
Ʋ Wire cross-section
0.5 mm² (AWG 20)
Ʋ Wire resistance
< 0.036 Ω/m (0.011 Ω/ft)
Ʋ Tensile strength
< 1200 N (270 lbf)
Ʋ Standard length
5 m (16.4 ft)
Ʋ Max. length
1000 m (3280 ft)
Ʋ Min. bending radius
25 mm (0.984 in) with 25 °C (77 °F)
Ʋ Diameter approx.
8 mm (0.315 in)
Ʋ Colour - standard PE
Black
Ʋ Colour - standard PUR
Blue
Ʋ Colour - Ex-version
Blue
Display and adjustment module
Voltage supply and data transmission
through the sensor
Indication
LC display in dot matrix
Adjustment elements
4 keys
Protection rating
Ʋ unassembled
IP 20
Ʋ mounted into the sensor without cover IP 40
Material
Ʋ Housing
ABS
Ʋ Inspection window
Polyester foil
Voltage supply
Operating voltage
Ʋ Non-Ex instrument
9 … 32 V DC
Ʋ Ex-ia instrument
9 … 24 V DC
Ʋ Ex-d instrument
16 … 32 V DC
Operating voltage with illuminated display and adjustment module
Ʋ Non-Ex instrument
12 … 32 V DC
Ʋ Ex-ia instrument
12 … 24 V DC
Ʋ Ex-d instrument
20 … 32 V DC
Power supply by/max. number of sensors
Ʋ Fieldbus
max. 32 (max. 10 with Ex)
Electrical protective measures
Protection, depending on housing version