beautypg.com

VEGA VEGACAL 65 Foundation Fieldbus User Manual

Page 39

background image

39

10 Supplement

VEGACAL 65 • Foundation Fieldbus

30035-EN-130917

Ʋ PTFE partly insulated: ø 8 mm

(0.315 in)

10 KN (2248 lbf)

Max. torque (process fitting - thread)

100 Nm (73 lbf ft)

Output variable
Output

Ʋ Signal

digital output signal, Foundation Fieldbus protocol

Ʋ Physical layer

according to IEC 61158-2

Channel Numbers

Ʋ Channel 1

Primary value

Ʋ Channel 2

Secondary value 1

Ʋ Channel 3

Secondary value 2

Transmission rate

31.25 Kbit/s

Current value

10 mA, ±0.5 mA

Damping (63 % of the input variable)

0 … 999 s, adjustable

Input variable
Measured variable

level of non-conductive liquids and solids

Measuring principle

phase-selective admittance processing (PSA)

Measuring range

0 … 3000 pF

Measuring frequency

270 kHz

Accuracy (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Temperature error

Ʋ < 120 pF

< 1 pF

Ʋ > 120 pF

1 % of the current measured value

Linearity error

< 0.25 % of the complete measuring range

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +80 °C (-40 … +176 °F)

Process conditions
Process pressure

Ʋ Standard

-1 … +64 bar/-100 … 6400 kPa (-14.5 … 928 psig)

Ʋ with screening tube adapter (PN1)

0 … +1 bar/0 … 100 kPa (0 … 14.5 psig)

Process temperature (thread or flange temperature)

Ʋ VEGACAL 65 of 316L with cable PT-

FE partly insulated ø 6 mm (0.236 in)

-50 … +150 °C (-58 … +302 °F)