VEGA VEGACAL 65 Foundation Fieldbus User Manual
Page 40
40
10 Supplement
VEGACAL 65 • Foundation Fieldbus
30035-EN-130917
Ʋ with temperature adapter [option
with cable PTFE insulated ø 6 mm
(0.236 in)]
-50 … +200 °C (-58 … +392 °F)
1
2
3
-50°C
(-58°F)
50°C
(122°F)
40°C
(104°F)
-40°C
(-40°F)
80°C
(176°F)
0°C
(32°F)
100°C
(212°F)
150°C
(302°F)
200°C
(392°F)
Fig. 25: Ambient temperature - Process temperature
1 Process temperature
2 Ambient temperature
3 Temperature range with temperature adapter
Dielectric constant
≥ 1.5
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Cable entry/plug
2)
Ʋ Single chamber housing
– 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x
blind plug M20 x 1.5
or:
– 1 x closing cap M20 x 1.5; 1 x blind plug M20 x 1.5
or:
– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT
or:
– 1␣x plug (depending on the version), 1␣x blind stopper
M20␣x␣1.5
Ʋ Double chamber housing
– 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm), 1 x
blind plug M20 x 1.5; 1 x blind plug M16 x 1.5 or
optionally available with 1 x plug M12 x 1 for external
display and adjustment unit
or:
– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT, 1 x blind
plug M16 x 1.5 or optionally 1 x plug M12 x 1 for exter-
nal display and adjustment unit
or:
– 1 x plug (depending on the version), 1 x blind plug
M20 x 1.5; 1 x blind plug M16 x 1.5 or optionally avail-
able with 1 x plug M12 x 1 for external display and
adjustment unit
Spring-loaded terminals for wire cross-
section
< 2.5 mm² (AWG 14)
2)
Depending on the version M12 x 1, according to DIN 43650, Harting, 7/8" FF.