VEGA VEGAPULS 68 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART two-wire User Manual

Page 57

background image

HART

output values

-

HART

value (Primary Value)

D

istance to the level

-

HART

value (Secondary Value)

D

istance to the level - scaled

S

ignal resolution

1.6 µA

F

ailure signal current output (adjustable)

mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
(

adjustable)

M

ax. output current

22

mA

L

oad

see load diagram under Power supply

D

amping (63 % of the input variable)

0 … 999

s, adjustable

F

ulfilled NAMUR recommendations

NE

43

Input variable

M

easured value

distance between process fitting and product sur-
face

M

ax. measuring range

70

m (229.7 ft)

M

in. distance from antenna end

400

mm (15.75 in)

Reference conditions to measuring accuracy (similar to DIN EN 60770-1)

R

eference conditions according to DIN EN 61298-1

-

T

emperature

+

18 … +30 °C (+64 … +86 °F)

-

R

elative humidity

45 … 75 %

-

A

ir pressure

860 … 1060

mbar/86 … 106 kPa (12.5 … 15.4 psig)

O

ther reference conditions

-

R

eflector

ideal reflector, e.g. metal plate 2 x 2 m

-

F

alse reflections

B

iggest false echo, 20 dB smaller than the useful

echo

Characteristics and performance data

F

requency

K-

band

I

nterval

approx. 1 s

B

eam angle -3 dB with horn antenna, depending on antenna diameter

-

ø

40

mm (1.575 in)

22°

-

ø

48

mm (1.89 in)

18°

-

ø

75

mm (2.953 in)

10°

-

ø

95

mm (3.74 in)

B

eam angle -3 dB with parabolic antenna

S

tep response or adjustment time

3)

>

1

s (dependent on the parameter setting)

3)

T

ime to output the correct level (with max. 10 % deviation) after a sudden

level change.

VEGAPULS

68 • 4 … 20

mA/HART two-wire

57

10 S

upplement

29261

-EN

-090305