VEGAPULS 51P … 54P

24890-EN-041227

Technical data

Ambient conditions

Vessel pressure
- VEGAPULS 51

process fitting PVDF

-100 … 300 kPa (-1 … 3 bar)

process fitting StSt

-100 … 1600 kPa (-1 … 16 bar)

- VEGAPULS 52

process fitting PVDF

-100 … 300 kPa (-1 … 3 bar)

process fitting StSt

-100 … 1600 kPa (-1 … 16 bar)

- VEGAPULS 53

-100 … 1600 kPa (-1 … 16 bar)

- VEGAPULS 54

-100 … 6400 kPa (-1 … 64 bar)

Ambient temperature on the housing

-40 … +80°C

Process temperature (flange temperature)
- VEGAPULS 51

process fitting PVDF

-20 … +80°C

process fitting StSt

-40 … +120°C

- VEGAPULS 52

process fitting PVDF

-20 … +120°C (briefly 130°C)

process fitting StSt

-40 … +150°C

- VEGAPULS 53

-40 … +150°C

VEGAPULS 54
- PTFE coupling (standard)

-25 … +150°C

- PTFE coupling (option)

-15°C/-30°C/-40 … +150°C

- ceramic coupling

-60 … +250°C

Storage and transport temperature

-60°C … +80°C

Protection

IP 66 and IP 67

Protection class

II

Overvoltage category

III

Ex-technical data

Comprehensive data see safety instructions manual (yellow binder)

WHG approvals

All VEGAPULS 51 … 54 radar sensors are approved as part of an overfill protection sys-
tem for stationary vessels storing water-endangering liquids.

Weights

VEGAPULS 51 and 52
- screwed connection G 1

1

/

2

A. 1

1

/

2

“ NPT 1.2 … 3.2 kg

- Tri-Clamp (DIN 32 676. ISO 2852)

2 … 5 kg

- R-connection (DIN 11 851)

2 … 6 kg

VEGAPULS 53 and 54
- DN 50

5.5 … 6 kg

- DN 80

7.3 … 8 kg

- DN 100

8.3 … 9 kg

- DN 150

13.1 … 13.8 kg

- ANSI 2“

4.8 … 5.4 kg

- ANSI 3“

6.6 … 7.1 kg

- ANSI 4“

10.2 … 10.8 kg

- ANSI 6“

14.3 … 15 kg