beautypg.com

Software addressing – VEGA VEGAPULS 51K…54K Profibus PA User Manual

Page 32

background image

32

VEGAPULS 51P … 54P

24890-EN-041227

Electrical connection

Example 2

You want to set address 27.
16 + 8 + 2 + 1 = 27

You must set the DIP switches
5 = 16
4 = 8
2 = 2
1 = 1
to „ON“.

Example 3

You want to set address 99
64 + 32 + 2 + 1 = 99

You must set the DIP switches
7 = 64
6 = 32
2 = 2
1 = 1
to „ON.

Software addressing

The DIP switches must be set to an address
of 126 … 255, i.e.

- either all DIP switches are set to „ON“,

corresponding to address 255 (delivery
status)

ON

Addr.

8 7 6 5 4 3 2 1

OFF

1

2

4

8

16

32

64

128

8 7 6 5 4 3 2 1

- or only DIP switch 8 is set to „ON“, corre-

sponding to address 128.

Of course, software addressing is also pos-
sible if the switches 7 … 2 are set to „ON“
(address 126).