VEGA VEGABAR 65 4 … 20 mA_HART User Manual

Page 55

background image

HART

output values

-

HART

value (Primary Value)

P

rocess pressure

-

HART

value (Secondary Value)

T

emperature

S

ignal resolution

1.6 µA

F

ailure signal current output (adjustable)

mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA

M

ax. output current

22

mA

L

oad

see load diagram under Power supply

F

ulfilled NAMUR recommendations

NE

43

Dynamic behaviour output

R

un-up time approx.

10

s

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 29: Sudden change of the process variable, dead time t

T

, rise time t

A

and step response time t

S

1

Process variable

2

Output signal

D

ead time

150

ms

R

ise time

100

ms (10 … 90 %)

S

tep response time

250

ms (ti: 0 s, 10 … 90 %)

D

amping (63 % of the input variable)

0 … 999

s, adjustable

Input variable

Adjustment

A

djustment range of the min./max. adjustment relating to the nominal measuring range:

-

percentage value

-10 … 110 %

-

pressure value

-20 … 120 %

VEGABAR

65 • 4 … 20

mA/HART

55

10 S

upplement

27531

-

EN

-081209