Nominal range

Overload, max. pressure Overload, min. pressure

0 … 100 bar/0 … 10 MPa

200 bar/20000 kPa

0 bar abs.

0 … 400 bar/0 … 40 MPa

800 bar/80000 kPa

0 bar abs.

Reference conditions and actuating variables (similar to DIN EN 60770-1)

Reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characteristics

linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

depending on the isolating diaphragm version

Deviation determined according to the limit point method according to IEC 60770

12)

Applies to digital interfaces (HART, Profibus PA, Foundation Fieldbus) as well as to analogue
current output 4 … 20 mA. Specifications refer to the set span. Turn down (TD) is the relation
nominal measuring range/set span.

Deviation

-

Turn down 1 : 1 up to 5 : 1

<

0.1 %

-

Turn down > 5 : 1

<

0.02 % x TD

Deviation with absolute pressure measuring range 0.1 bar

-

Turn down 1 : 1 up to 5 : 1

<

0.25 %

-

Turn down > 5 : 1

<

0.05 % x TD

Influence of the product or ambient temperature

Applies to instruments with digital signal output (HART, Profibus PA, Foundation Fieldbus) as well
as to instruments with analogue current output 4 … 20 mA. Specifications refer to the set span.
Turn down (TD) = nominal measuring range/set span.

Thermal change zero zignal, reference temperature 20 °C (68 °F):

-

In the compensated temperature range
0 … +100 °C (+32 … +212 °F)

<

0.05 %/10 K x TD

-

Outside the compensated temperature
range

typ. < 0.05 %/10 K x TD

Applies also to instruments with analogue 4 … 20 mA current output and refers to the set span.

Thermal change, current output

<

0.15 % at -40 … +80 °C (-40 … +176 °F)

12)

Incl. non-linearity, hysteresis and non-repeatability.

56

VEGABAR

61 • Profibus PA

10 Supplement

28251

-EN