Adjustment steps – VEGA Capacitive electrodes EK 4 … 20 mA - Compact User Manual
Page 31
Capacitive electrodes EK 4 … 20 mA - Compact
31
22574-EN-020809
Setup
Adjustment steps
On the following pages you will see the menu
schematic of the HART
®
handheld in conjunc-
tion with capacitive electrodes.
The most important adjustment steps are
marked in the menu schematic with the letters
A … D.
General information on the HART
®
handheld:
If you have entered or modified parameters,
you have to push the „
ENTER“ key. The ad-
justment is saved in the handheld, but not in
the sensor itself.
After you have pushed „
ENTER“, you have to
push „
SEND“ to transfer the settings to the
sensor.
After pushing „
SEND“, a warning is displayed.
If you push „
OK“, the setting is transferred to
the sensor.
In a further safety enquiry you are asked to
switch the system from manual to automatic
operation. Confirm with „
OK“.
With
„HOME“ you return to the initial menu.
Generic: SENSOR
PV LRV
0.000 m
10.000
HELP DEL ABORT ENTER
4.1
(5.1)
Empty adjustment without
medium
Generic: SENSOR
1 PV
LRV
2 PV
URV
HELP SEND
HOME
Generic: SENSOR
- WARNING-
Pressing ”OK“ will
change device output.
Put loop in manual
ABORT OK
Generic: SENSOR
- WARNING-
Return control loop to
automatic control.
OK
Generic: SENSOR
1 PV
LRV
2 PV
URV
HELP
HOME