VEGA Capacitive electrodes EK 4 … 20 mA - Compact User Manual

Page 27

background image

Capacitive electrodes EK 4 … 20 mA - Compact

27

22574-EN-020809

Setup

Mode 2 = Phase angle 45°

The capacitance and the ohmic conductance
are measured separately, the capacitance
value is corrected by calculating it with the
ohmic conductance, so that measurement
errors caused by conductive buildup or vary-
ing product moisture are compensated.
Application:
- highly conductive products
- adhesive, conductive products
- solids with fluctuating moisture content

For applications in conductive, viscous liquids,
you should use a suitable electrode of type EK
24.

(+/-)

Mode 1 (90°)

(–)

Mode 1 (90°)

(+)

Mode 2 (45°)

7 Simulation current

With this function you can simulate the level.
As soon as the rotary switch is set to position
7, the simulation will be active. The current
value of the instantaneous level is used as the
initial simulation value. With the plus and minus
key you can modify the current value between
3.8 mA and 22 mA. Each push of the key
changes the current value by a 10 µA incre-
ment.
If you hold the key pushed, the value changes
automatically and with rising speed.

(+)

increase current

(-)

reduce current

8 Reset

This function sets all values to default.
Take note that also the adjustment will be
deleted. Tag number, measurement loop des-
ignation etc. from the HART

®

or VVO adjust-

ment, however remain unchanged.

(+/-)

Default

Default

0 Operate

---

1 Min. adjustment

4 mA at 0 pF

2 Max. adjustment

20 mA at 3000 pF

3 Integration time

0.5 s

4 Reverse charact.

4 ... 20 mA

5 Linearisation

Off

6 Sensor optimisation Mode 1 (90°)
7 Simulation current

Off

8 Reset

---

9 Offset correction

already saved values
remain

9 Offset correction

This function is necessary if an adjustment
should be carried out in m. This is only possi-
ble in conjunction with the CAP E 32 H Ex
oscillator. With this function, the initial capaci-
tance in the electronics is saved. A prerequi-
site is that the electrode is mounted into the
vessel and that it is completely uncovered by
the medium.

For electrodes with concentric tube, this func-
tions is already carried out at VEGA as the
vessel does not influence the measurement.
The offset correction must only be repeated if
the oscillator is exchanged.

(+/–)

Initial capacitance is saved