2 connection examples for overvoltage arresters, Vessel with cathodic tank protection, 2 technical information – VEGA VEGATROL 10 Ex 1 User Manual
Page 11: Cu-line
VEGATROL 10 Ex 1
11
E2
E1
A2
A1
A1
A2
E2
E1
1
2
Typ
B62-27
Typ
B62-27G
d30
d32
E2
E1
A2
A1
A1
A2
E2
E1
1
2
Typ
B62-27
Typ
B62-27G
d30
d32
2 Technical Information
2.5.2 Connection examples for overvoltage arresters
Vessel without cathodic tank protection
to potential
equalization line
min. 4 mm
2
Cu
External earth terminal
either
overvoltage arrester
Note:
- Suitable cable must be used, either with metal cover (or screen). If a
cable with metal cover or screen is used (as on above figure), a potential
equalization along the entire length of the intrinsically safe circuit is not
necessary. Screen or metal cover must only be connected to the
overvoltage arrester.
- The current load capacity of the screen must correspond at least to that
of a 1,5 mm
2
Cu-line.
Earth / PA
connection terminal
Outer isolation
Outer isolation
Screen
Screen
Ex-area
Not Ex-area
(control room)
Overvoltage arrester
min. 4 mm
2
Cu
Screen
either
overvoltage arrester
Note:
- Suitable cable must be used with metal cover (or screen). Screen or metal
cover must only be connected to the overvoltage arrester. Screen or
metal cover must not be earthed.
- The cable must have an outer isolation.
- The current load capacity of the screen must correspond at least to that
of a 1,5 mm
2
Cu-line.
Earth / PA
connection terminal
Outer isolation
Ex-area
Not Ex-area
(control room)
Vessel with cathodic tank protection
Screen
Line length
≤
50 m
Metal housing isolated or
plastic housing
Overvoltage arrester
Type B 62 - 27 Ex 0-2
or B 62 - 27 Ex-2
Overvoltage arrester
Line length
≤
50 m
Metal housing isolated or
plastic housing
Overvoltage arrester
Type B 62 - 27 Ex 0 - 2
or B 62 - 27 Ex - 2
Outer isolation
External
earth terminal
Cathodic tank protection
2 … 24 V
(object voltage)
VEGASWING
E86 Ex
VEGASWING
E86 Ex
VEGATOR
526 W Ex
VEGATOR
526 W Ex