Page 35: Electrical connection
VEGAPULS 42, 44 and 45 – Profibus PA
35
24908-EN-041227
Electrical connection
ESC
ESC
+
-
OK
OK
–
+
+1
2-
5
6
7
8
Display
Bus
Addr.
ON
8 7 6 5 4 3 2 1
Power supply and
Profibus signal
To the indicating instrument in the
sensor lid or to the external
indicating instrument VEGADIS 50
Version with aluminium housing
+
-
-
OK
+
ESC
Tank 1
m (d)
12.345
+1
2-
5
6
7
8
Display
Bus
Addr
.
ON
8 7 6 5 4 3 2 1
Power supply and
Profibus signal
Version with plastic housing
To the display in the lid or
the external indicating
instrument
M20 x 1.5
(diameter of the
connection cable
6…9 mm)
Spring-loaded terminals
(max. 2.5 mm
2
wire
cross-section)
Opening tabs
Pluggable
adjustment
module
MINICOM
4.3 Connection of the sensor
After mounting the sensor at the measure-
ment location according to the instructions in
chapter "3 Mounting and installation“, loosen
the closing screw on top of the sensor. The
sensor lid with the optional indication display
can then be opened. Unscrew the sleeve nut
and slip it over the connection cable (after
removing about 10 cm of insulation). The
sleeve nut of the cable entry has a self-lock-
ing ratchet that prevents it from opening on
its own.
Now insert the cable through the cable entry
into the sensor. Screw the sleeve nut back
onto the cable entry and clamp the stripped
wires of the cable into the proper terminal
positions.
The terminals hold the wire without a screw.
Press the white opening levers with a small
screwdriver and insert the copper core of the
connection cable into the terminal opening.
Check the hold of the individual wires in the
terminals by lightly pulling on them.
M20 x 1.5
(diameter of the
connection cable
6…9 mm)