22

VEGAPULS 42, 44 and 45 – Profibus PA

24908-EN-041227

ш 5...15

ш 5...15

Openings in a surge pipe for mixing of inhomogene-
ous products

slightly inhomogeneous
liquids

inhomogeneous liquids

homogeneous
liquids

VEGAPULS 45 with integrated measuring tube (surge
pipe) carries out the measurement in between heating
spirals

Standpipe measurement of inhomoge-
neous products

Mounting and installation

VEGAPULS 45 with integrated measur-
ing tube

VEGAPULS 45 sensor version was especially
developed for measuring tube applications
and is supplied complete with a 27 mm
measuring tube. With a measuring tube
length up to 4 m, this sensor version was
designed to be used, e.g. in existing stand-
pipes.

VEGAPULS 45 with integrated measuring tube in the
vessel or in an existing bypass tube

max

min

Note:

VEGAPULS 45 sensors with an integrated
measuring tube are provided with a screwed
process connection or a flange connection.
For sensors with screwed thread as process
connection, make sure that during screwing
in the entire sensor turns, i.e. also the sensor
housing. The sensor housing is fastened with
a clamping connection to the measuring tube.
This sensor housing must not be turned with
respect to measuring tube or even loosened.
Otherwise, the radar signal coupling would
be destroyed and the sensor would no
longer function.