VEGAPULS 42, 44 and 45 – Profibus PA

23

24908-EN-041227

ø50

> 300 mm

Tube antenna system with ball valve cutoff in measur-
ing tube

Ball valve

Vent hole

Deflector

Surge pipe with ball valve

If a ball valve is mounted in the surge pipe,
maintenance and servicing can be carried
out without opening the vessel (e.g. if it con-
tains liquid gas or toxic products).

A prerequisite for trouble-free operation is a
ball valve throat that corresponds to the pipe
diameter. The valve must not have rough
edges or constricted areas in its channel.
The distance to the sensor flange should be
at least 300 mm.

If you want to measure inhomogeneous or
stratified products in a surge pipe, it must
have holes, elongated holes or slots. These
openings ensure that the liquid is mixed and
corresponds to the liquid in the vessel.

The more inhomogeneous the measured
product, the closer the openings should be
spaced.

Due to radar signal polarisation, the holes or
slots must be positioned in two rows offset
by 180°. The radar sensor must then be
mounted so that the type label of the sensor
is aligned with the rows of holes.

Every wider slot causes a false echo. The
slots should therefore not exceed a width of
10 mm in order to keep the signal noise level
to a minimum. Round slot ends are better
than rectangular ones.

Mounting and installation

ø 5...15

VEGAPULS 44: Row of holes on same axis as type
label

Type label