VEGA VEGATOR 622 User Manual
Page 6
6
VEGATOR 620 … 622
Product description
Additional measurement data input on VEGATOR 620
Number
1 additional current input
Input type
passive two-wire input analogue
Range
4 … 20 mA
Inner resistance
22 Ohm
Application
switching in series with active inputs of e.g.
VEGATOR 620, VEGAMET 601
Hysteresis
80 µA
Temperature error
0.05 %/10 K of range
Relay output
Number
1 output
Contact
1 spdt
(12 - 13 open, 12 - 14 close)
Contact material
AgCdO and Au plated
Switching voltage
min. 10 mV DC
max. 250 V AC, 250 V DC
Switching current
min. 10 µA DC
max. 3 A AC, 1 A DC
Breaking capacity
max. 750 VA, 54 W
Transistor output (not on VEGATOR 620)
Number
1 output
(synchronously switching with the relay outputs)
Switching voltage U
CE
max. 36 V DC
Switching current I
C
max. 60 mA DC (short circuit proof, transistor
limits the current in case of short circuit to a
stand-by current of approx. 5 mA)
Voltage loss U
CE
- 1.5 V at I
B
= 60 mA
Blocking current I
O
< 10 µA
Electrical connection
Screw terminal
max. 1.5 mm
2
Electrical protective measures
Protection
- instrument
IP 30
- socket
IP 20
Protection class
II
Overvoltage category
II
Mechanical data
Mounting
carrier rail mounting acc. to DIN 46 277, p. 3
Dimensions
W = 36 mm, H = 118.5 mm, D = 134 mm
Weight
approx. 170 g