beautypg.com

VEGA VEGATOR 622 User Manual

Page 6

background image

6

VEGATOR 620 … 622

Product description

Additional measurement data input on VEGATOR 620

Number

1 additional current input

Input type

passive two-wire input analogue

Range

4 … 20 mA

Inner resistance

22 Ohm

Application

switching in series with active inputs of e.g.
VEGATOR 620, VEGAMET 601

Hysteresis

80 µA

Temperature error

0.05 %/10 K of range

Relay output

Number

1 output

Contact

1 spdt
(12 - 13 open, 12 - 14 close)

Contact material

AgCdO and Au plated

Switching voltage

min. 10 mV DC

max. 250 V AC, 250 V DC

Switching current

min. 10 µA DC
max. 3 A AC, 1 A DC

Breaking capacity

max. 750 VA, 54 W

Transistor output (not on VEGATOR 620)

Number

1 output
(synchronously switching with the relay outputs)

Switching voltage U

CE

max. 36 V DC

Switching current I

C

max. 60 mA DC (short circuit proof, transistor
limits the current in case of short circuit to a
stand-by current of approx. 5 mA)

Voltage loss U

CE

- 1.5 V at I

B

= 60 mA

Blocking current I

O

< 10 µA

Electrical connection

Screw terminal

max. 1.5 mm

2

Electrical protective measures

Protection
- instrument

IP 30

- socket

IP 20

Protection class

II

Overvoltage category

II

Mechanical data

Mounting

carrier rail mounting acc. to DIN 46 277, p. 3

Dimensions

W = 36 mm, H = 118.5 mm, D = 134 mm

Weight

approx. 170 g