4 technical data and dimensions – VEGA VEGATOR 622 User Manual
Page 5
VEGATOR 620 … 622
5
Product description
1.4 Technical data and dimensions
General data
Power supply
Operating voltage
20 … 72 V DC
20 … 250 V AC, 50/60 Hz (sine)
in case of emergency power supply with curve
form extremely deviating from sine: max.
125 V AC (rectangle)
Power consumption
max. 3 W (3 … 18 VA)
Fuse
- supply range
T 1 A, 250 V
Measurement data input, general
Number
1 current input
Input type
active two-wire input analogue
Range
4 … 20 mA
Sensor
capacitive probes
hydrostatic pressure transmitters
process pressure transmitters
Sensor supply voltage
- VEGATOR 620
24 V DC
- VEGATOR 621, 622
15 … 18 V DC
Switching threshold
4 … 20 mA adjustable
Min. hysteresis
- VEGATOR 620, 621
80 µA
- VEGATOR 622
80 … 16000 µA
Current limitation
at 24 mA, permanently shortcircuit proof
Temperature error
0.05 %/10 K of range
Connection cable
2-wire (standard cable)
Resistance per wire
- VEGATOR 620
max. 250 Ohm
- VEGATOR 621, 622
max. 35 Ohm
off
off
on
VEGATOR 622 double point level
switch
Time t
Max.
Min.
Level
Ex area
Non-Ex area
VEGATOR 622
Double point level switch
with fault monitoring, adjustable switching hysteresis, se-
lectable mode A/B (A = overfill protection, B = dry run pro-
tection) and with adjustable integration time
Input:
1 capacitive electrode
1 hydrostatic pressure transmitter
1 process pressure transmitter
Outputs:
1 relay (spdt)
1 transistor
Approvals:
[EEx ia] IIC,
as part of an overfill protection acc. to WHG
Application:
Min./max. control, overfill protection, dry run
protection