beautypg.com

VEGA VEGATOR 636 Ex Ship approvals User Manual

Page 22

background image

22

7 Maintenance and fault rectification

VEGATOR 636 Ex • Signal conditioning instrument

23446-EN-130627

Error

Cause

Rectification

The red failure control

lamp (LED) of the signal

conditioning instrument

lights

Current value < 2.3 mA

– Measure the current value on the signal cable to the

sensor

– Check all connections and connection cables to the

sensor

– The voltage should be approx. 17 … 20 V

– If the value is below 17 V, probably the signal condi-

tioning instrument is defective.

– Exchange the signal conditioning instrument or send

it for repair

– If the red failure lamp continues to light, separate

the sensor from the connection cable and connect

a resistor of 1 kΩ instead on the signal conditioning

instrument

– If the failure lamp continues to light, the signal condi-

tioning instrument is defective

– Exchange the signal conditioning instrument or send

it for repair

– Should the failure lamp extinguish, you can connect

the sensor again. Separate the signal conditioning

instrument from the connection cable and connect a

resistor of 1 kΩ to the sensor input

– If the failure lamp continues to light, the connection

cable is probably interrupted

– Check the connection cable to the sensor

– Should the failure lamp extinguish, the sensor will be

defective

– Exchange the sensor or send it in for repair

The red failure control

lamp (LED) of the signal

conditioning instrument

lights

Current value > 23.2 mA

Measure the current value on the signal cable to the

sensor

– Check all connections and connection cables to the

sensor

– If the red failure lamp continues to light, separate

the sensor from the connection cable and connect

a resistor of 1 kΩ instead on the signal conditioning

instrument

– If the failure lamp extinguishes, the sensor is defec-

tive. Check the connected sensor

– If the failure lamp continues to light, connect the sen-

sor again. Separate signal conditioning instrument

from the connection cable and connect a resistor of

1 kΩ to the sensor input.

– If the failure lamp extinguishes, this is probably due

to a shortcircuit in the connection cable

– Check the connection cable to the sensor

– If the failure lamp continues to light, the signal condi-

tioning instrument is defective

– Exchange the signal conditioning instrument or send

it for repair

Malfunction during func-

tion test

After pushing the test key,

the switching conditions

do not occur in the correct

sequence or correct du-

ration, e.g. no full signal is

outputted.

– Measure the line resistance

– If the cable is highly resistive, bring it to a normal

resistance, e.g. check terminals and cable connec-

tions on corrosion