beautypg.com

7 maintenance and fault rectification, 1 maintenance, 2 rectify faults – VEGA VEGATOR 636 Ex Ship approvals User Manual

Page 21

background image

21

7 Maintenance and fault rectification

VEGATOR 636 Ex • Signal conditioning instrument

23446-EN-130627

7 Maintenance and fault rectification

7.1 Maintenance

If the instrument is used properly, no special maintenance is required

in normal operation.

7.2 Rectify faults

A maximum of reliability is ensured. Nevertheless, faults can occur

during operation. These may be caused by the following, e.g.:

Measured value from sensor not correct

Voltage supply

Interference on the cables

The first measure to be taken is to check the input and output signals.

The procedure is described as follows. In many cases the causes can

be determined this way and faults can be easily rectified.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the

English language. The service is free of charge, only the standard

telephone costs will be charged.

Error

Cause

Rectification

The red failure control

lamp (LED) of the signal

conditioning instrument

lights

Sensor not connected cor-

rectly

– In Ex systems, make sure that the Ex protection is not

influenced by the measuring instruments used.

– Measure the current value on the signal cable to the

sensor

– Faults on the sensor causing a current change below

2.3 mA or above 23.2 mA, cause a fault signal on

measuring instruments.

Sensor not connected cor-

rectly

– In Ex systems, make sure that the Ex protection is not

influenced by the measuring instruments used.

– Measure the voltage on the connection cable

– The terminal voltage of the sensor is at least 12 V in

normal condition

Failure reasons

Fault rectification

24 hour service hotline

Fault