3 shorten suspension cable – VEGA VEGAWELL 72 4 … 20 mA_HART User Manual
Page 29
?
4 … 20
mA signal missing
l
W
rong connection to power supply
à Check connection according to chapter "Connection
steps" and if necessary, correct according to chapter
"Wiring plan"
l
N
o voltage supply
à Check cables for breaks; repair if necessary
l
supply voltage too low or load resistance too high
à Check, adapt if necessary
?
C
urrent signal 3.6 mA; 22 mA
l
electronics module or measuring cell defective
à Exchange instrument or return instrument for repair
I
n Ex applications, the regulations for the wiring of intrinsically
safe circuits must be observed.
D
epending on the failure reason and measures taken, the
steps described in chapter "Set up" must be carried out again,
if necessary.
8
.3 Shorten suspension cable
T
he suspension cable can be shortened individually. For the
version with plastic or stainless steel housing proceed as
follows:
1
U
nscrew the housing cover
2
L
oosen the screw terminals and remove the wire ends of
the suspension cable out of the screw terminals
3
H
old the hexagon on the screwed socket with SW 46 and
loosen with seal screw SW 22
Caution:
S
eal screw is secured with Loctide pink, mote breakaway
torque!
Reaction after fault rec-
tification
VEGAWELL
72 • 4 … 20
mA/HART
29
8 M
aintenance and fault rectification
27630
-
EN
-080806