VEGAKON

3

1.2 Types and versions

VEGAKON 61

Application:
-

single point control

Series:
-

compact instrument, with socket G 1 A or cone
DN 25 with compression nut

Power supply:
-

with relay module

20 … 72 v DC
20 … 250 V AC, 50/60 Hz

-

with transistor module
10 … 55 V DC

Output:

-

relay module with one spdt or

-

transistor module

VEGAKON 63

as VEGAKON 61, however with extension tube
between socket or cone DN 25 with compression nut

and annular electrode.

Extension tube:
-

70 … 4000 mm with socket

-

60 … 4000 mm with cone DN 25

Optional fitting G 1

1

/

2

A for height adjustment is

available.

1.3 Approvals

GL-approval

For compact instruments as certified products acc. to
the regulations of the German Lloyd
-

Conductive compact instrument VEGAKON 61

-

Conductive compact instrument VEGAKON 63

defined in certificate

no. 96 712 - 95 HH

.

CE-approval

The compact instruments meet with the protective
regulations of EMVG (89/336/EWG) and NSR
(73/23/EWG). The conformity is acc. to the following
standards:
EMVG

Emission

EN 50 081-1

Immission

EN 50 082-2

NSR

EN 61 010

Product description

1 Product description

1.1 Function and configuration

VEGAKON compact level switches detect levels of
conductive liquids.

Annular electrode (3-elements), oscillator and power
supply form one unit. The modular construction of the
oscillator allows installation in virtually any application..

When the electrode is covered by the product, small

alternating currents (< 1 mA) flow from the meas.
electrode to the reference and neutralization electrode.

1

2

3

1 Reference electrode

(mounting boss)

2 Meas. electrode

3 Neutralization

electrode

Fig. 1 Annular electrode

These alternating currents are measured in respect to
their amplitude and phase position and processed into
a switching signal.

Acc. to the oscillator (module) a relay gets energized
or de-energized or the transistor output is conductive
or blocked (mode A or B) see "4.1 Indicating and
operating elements".

Product build-up is eliminated via the neutralization
electrode; the conductivity is measured and the switch
point sensitivity is automatically adjusted.

VEGAKON can be therefore used for reliable detection
of products over a very wide conductivity and viscosity
range.