8 Maintenance and fault rectification

8.1 Maintenance

W

hen used in the correct way, no special maintenance is required in

normal operation.

8.2 Remove interferences

T

he operator of the system is responsible for taken suitable measures

to remove interferences.

A

maximum of reliability is ensured. Nevertheless, faults can occur

during operation. These may be caused by the following, e.g.:

l

S

ensor

l

P

rocess

l

P

ower supply

l

S

ignal processing

T

he first measures to be taken are to check the output signals as well

as to evaluate the error messages via the indicating and adjustment
module. The procedure is described below. Further comprehensive
diagnostics can be carried out on a PC with the software PACTware
and the suitable DTM. In many cases, the causes can be determined
in this way and faults can be rectified.

H

owever, should these measures not be successful, call the VEGA

service hotline in urgent cases under the phone no. +49 1805 858550.

T

he hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the
E

nglish language. The service is free of charge, only the standard

telephone costs will be charged.

C

onnect a handheld multimeter in the suitable measuring range

according to the wiring plan.

?

4 … 20

mA signal not stable

l

L

evel fluctuations

à Set damping via the indicating and adjustment module

?

4 … 20

mA signal missing

l

W

rong connection

à Check connection according to chapter "Connection steps"

and if necessary, correct according to chapter "Wiring plan"

l

N

o power supply

à Check cables for breaks; repair if necessary

l

O

perating voltage too low or load resistance too high

à Check, adapt if necessary

Reaction when malfunc-
tions occur

Causes of malfunction

Fault rectification

24 hour service hotline

Checking the 4 … 20 mA
signal

VEGAPULS

65 • 4 … 20

mA/HART four-wire

39

8 M

aintenance and fault rectification

28442

-EN