Fig. 8: Recommended socket mounting

I

n case of very big socket diameters, the active antenna part can be

slightly recessed in the socket. The following rule applies to the
standard version of VEGAPULS 65: Socket diameter corresponds to
max. socket height.

A

lign the sensor in liquids as vertical as possible to the product surface

to achieve optimum measurement.

Fig. 9: Alignment in liquids

T

he mounting location of the radar sensor should be a place where no

other equipment or fixtures cross the path of the microwave signals.

V

essel installations such as, for example, ladders, limit switches,

heating spirals, struts, etc. can cause false echoes that get super-
imposed on the useful echo. Make sure when planning your measuring
site that the radar sensor has a "clear view" to the measured product.

I

n case of existing vessel installations, a false echo storage should be

carried out during setup.

I

f large vessel installations such as struts or supports cause false

echoes, these can be attenuated through supplementary measures.
S

mall, inclined sheet metal baffles above the installations scatter the

radar signals and prevent direct interfering reflections.

Sensor orientation

Vessel installations

VEGAPULS

65 • 4 … 20

mA/HART four-wire

17