Fig. 4: Position of the polarisation plane with VEGAPULS 65

1

Marking hole

M

ake sure that all parts of the instrument in contact with the measured

product, especially the sensor element, process seal and process

tting, are suitable for the existing process conditions such as process

pressure, process temperature as well as the chemical properties of
the medium.

Y

ou can find the specifications in chapter "Technical data" in the or on

the type label.

4.2 Mounting instructions

T

he flange screws of VEGAPULS 65 must be always screwed with the

torque stated in the technical data so that the PTFE washer of the
encapsulated antenna system seals.

Y

ou can counteract the material-induced tension loss with PTFE by

doing the following:

1

M

ake sure the number of flange screws corresponds to the

number of flange holes

2

U

se disc springs in addition to the flange screws for fastening the

ange

3

T

ighten the screws steadily with the torque specified in the

technical data

Suitability for process
conditions

Mounting of instruments
with PTFE-coated
flanges

14

VEGAPULS

65 • 4 … 20

mA/HART four-wire