3features – Velleman VMB1RY User Manual
Page 3
Velbus manual VMB1RY– edition 1 – rev.1.0
3
Features:
◊ Relay output: changeover contact (N.O. and N.C.)
◊ Switching capacity with a resistive load: 16A/230Vac max.
◊ Switching capacity with an inductive load: 8A/230Vac max.
◊ Suppressed relay contacts.
◊ Manual control on the module
◊ LED indicators for:
• Relay output
• Operation modes (slow, fast, very fast or 2 x blinking and continuously ON)
• Power voltage
• Data reception and forwarding through VELBUS
◊ 10 different operation modes (adjustable through ‘mode’l rotary switch):
• Moment control
• On/off control
• Start/stop timer
• Staircase lighting timer
• Non-restartable timer
• Switch-off delay
• Switch-on delay
• Start timer by releasing push button
• Timer with blinking effect
• 2-way timer (short press will start timer 1/ long press will start timer2)
◊ 16 possible time settings (adjustable through ‘time1’ rotary switch): moment - 5s - 10s - 15s - 30s - 1min - 2 min
- 5min - 10min - 15min - 30min – 1h – 2h – 5h – 1day – on/off
◊ 9 possible time settings for timer 2 (adjustable through ‘time2’ rotary switch): 5min - 10min - 15min - 30min – 1h
– 2h – 5h – 1day – on/off
◊ Controllable by connecting several push buttons in parallel.
◊ Push button input debounce: 65ms.
◊ Control through VELBUS.
◊ Programmable without PC.
◊ Easy learning process by controlling the push buttons in the learning mode.
◊ 8 different control possibilities:
• Using push buttons turning on the relay.
• Using push buttons turning off the relay.
• Using push buttons turning the relay on or off.
• Using push buttons activating the set mode on the module.
• Using push buttons starting or stopping the timer.
• Using push buttons starting or stopping the 2nd timer.
• Using push buttons starting or restarting the timer.
• Using push buttons starting or restarting the 2nd timer.
◊ Memory for 7 different push buttons per command
◊ Learned push buttons are saved in case of a power failure.
◊ Report to control modules for LED status modification.
◊ 247 possible addresses (adjustable through ‘ADDR” rotary switch)
◊ Required power voltage: 12 to 18VDC
◊ Consumption in standby: 35mA at 18V (15mA at 16V)
◊ Consumption activated relay: 85mA at 18V (60mA at 16VDC)
◊ Max. consumption (activated relay and push button input): 100mA at 18V (75mA at 16VDC)
◊ Standard DIN-rail housing (2 modules)
◊ Dimensions (L x W x H): 90 x 36 x 58mm.
◊ Weight: 100g.