beautypg.com

Connecting the fcs-320-tp/-tt series, Parameter settings using the dip switch, Commissioning – Bosch FCS-320-TP Series Conventional Aspirating Smoke Detectors User Manual

Page 27

background image

FCS-320-TP1 | FCS-320-TP2 | FCS-320-TT1 | FCS-320-TT2

en

27

Bosch Sicherheitssysteme GmbH

F.01U.130.927 | 2.0 | 2010.12

Connecting the FCS-320-TP/-TT series
See Figure 4, Page 5:

Parameter Settings Using the DIP Switch
The aspirating smoke detector parameters are set using the DIP switch on the detector
modules. The default settings are marked in bold in each case. Select all other parameters
(see tables).

Commissioning
See Figure 5, Page 5:

Terminal Terminal block X7
1

Fault 2

Fault contact for 2nd detector module

2
3

Al 2

NO contact for 2nd alarm relay

4

C contact for 2nd alarm relay

5

NC contact for 2nd alarm relay

6

+ Ext. Displ.2

Remote indicator for 2nd detector module

7

- Ext. Displ.2

8

Fault 1

Fault contact for 1st detector module

9

Sensitivity

DIP settings

DM-TP-01(05)
DM-TT-01(05)

DM-TP10(25)
DM-TT-10(25)

DM-TP50(80)
DM-TT-50(80)

Switch 1

Switch 2

0,12 %/m(0,4 %/m) 0,8 %/m(2 %/m)

on

on

0,06 %/m(0,2 %/m) 0,4 %/m(1 %/m)

off

on

0,03 %/m(0,1 %/m) 0,2 %/m(0,5 %/m)

1,0 %/m(1,6 %/m)

on

off

0,015 %/m(0,05 %/
m)

0,1 %/m(0,25 %/m) 0,5 %/m(0,8 %/m)

off

off

Alarm delay

DIP settings

Switch 3

Switch 4

0 seconds

off

off

10 seconds

on

off

30 seconds

off

on

60 seconds

on

on

Activation threshold for airflow malfunction

DIP settings

Switch 5

Switch 6

Low (+/- 10% volume flow change)

on

off

Average (+/- 20% volume flow change)

off

on

High (+/- 30% volume flow change)

off

off

Very high (+/- 50% volume flow change)

on

on

Airflow fault delay

DIP settings

Switch 7

Switch 8

30 seconds

off

on

2 minutes

on

off

15 minutes

on

on

60 minutes

off

off

Trouble logging

DIP settings

LOGIC·SENS filter

DIP settings

Switch 9

Switch 10

not saving

off

off

off

saving

on

on

on

NOTICE!

The sensitivity value is based on measurements with standard test fires (old value in
brackets).
The activation threshold for the airflow malfunction is set to 20% volume flow change by
default. Higher values are not permitted within EN 54-20.