15.1.5 SB 650/3 AC
1305
965
450
1850
1725
1480
1135
560
125
125
750
690
50
950
c01
d33
c10
d34
c06
i02
i03
i04
i18
D
00000
17
58
7
SB 650/3 AC
c01 Cold water inlet
Male thread
G 1 1/2 A
c06 DHW outlet
Male thread
G 2 A
c10 DHW circulation
Male thread
G 1/2
d33 Heat source flow
Male thread
G 3/4 A
d34 Heat source return
Male thread
G 3/4 A
h43 Thermometer
Male thread
G 1/2 A
i02 Flange I
Diameter
mm
280
Pitch circle diameter
mm
245
Screws
12 x M14
Torque
Nm
85
i03 Flange II
Diameter
mm
280
Pitch circle diameter
mm
245
Screws
12 x M14
Torque
Nm
85
i04 Flange III
Diameter
mm
280
Pitch circle diameter
mm
245
Screws
12 x M14
Torque
Nm
85
i07 Electric emergency/booster
heater
Female thread
G 1 1/2
i18 Protective anode
15.2 Fault conditions
In the event of a fault, temperatures of up to 95 °C at 0.6 MPa
can occur.
15.3 Data table
SB 302 S
SB 402 S
SB 602 AC
SB 1002 AC
SB 650/3 AC
185354
185355
071554
071282
003039
Hydraulic data
Nominal capacity
l
300
400
600
1000
650
Application limits
Max. permissible temperature
°C
110
110
110
110
110
Max. permissible pressure
MPa
1.0
1.0
1.0
1.0
1.0
Test pressure
MPa
1.5
1.5
1.5
1.5
1.5
Max. flow rate
l/min
38
45
50
70
50
Versions
Sealed unvented type
Dimensions
Height
mm
1585
1755
1685
2525
1725
Width
mm
700
750
750
750
750
Depth
mm
700
750
800
800
830
Weight
Weight (full)
kg
401
519
754
1212
840
Weight (empty)
kg
101
119
154
212
190