16
If none of the above remedies help to solve your problem, contact
your local dealer for further help.
CHARGE BATTERY or
CHARGE BATTERY
FULL flashes
•
Charge battery full (equalize/
synchronize your battery with
the monitor)
•
Check the charged parameters
in Functions F02, F03 and F04
for possible incorrect setting
s.
State-of-charge and/or
time-to-go readout are
not accurate
•
Check if all current is flowing
through the shunt (the negative
terminal of the battery may only
contain the wire going to the
battery side of the shunt!).
•
Current sense leads from the
shunt are reversed.
•
Check battery capacity in
Function F01
•
Check CEF in Function F09
•
Check Peukert Exponent in
Function F10
•
Check Battery temperature in
Function F11
•
Check Temperature coefficient
in Function F12
Display returns “- - - -” in
temperature readout
Connection with temperature
sensor is lost. Check for failed
connections and/or cable damage.
Battery voltage readout is
highly inaccurate
Check prescaler setting in Function
F16