Xantrex Technology Xantrex Battery Monitor User Manual
Page 15
6
F06
Low-battery alarm OFF. When the state-of-charge
percentage has risen above this value and the alarm relay
is activated, the alarm relay will be deactivated again.
When FULL is selected the alarm relay is deactivated
when the charged parameters are met.
Default
Range
Step size
80.0%
0.0 – 100.0% /
FULL
1.0%
F07
Under-voltage alarm. When the battery voltage falls
below this value, after 10 seconds the message Lo will
appear on the display and the alarm relay will be
activated.
Default
Range
Step size
10.5 V
OFF / 8.0 – 33.0 V
0.1 V
F08
Over-voltage alarm. When the battery voltage rises above
this value, after 5 seconds the message Hi shall appear on
the display and the alarm relay will be activated.
Default
Range
Step size
16.0 V
OFF / 10.0 – 35.0 V
0.1 V
F09
Charge efficiency factor (CEF). It is recommended to
keep this value at AU (automatic calculation). The value
A90 resets the automatic calculation to 90%. A manual
setting is represented by Uxx where xx is the charge
efficiency. (See page 2 for more info about CEF.)
Default
Range
Step size
AU
U50 – U99 / AU /
A90
1%
F10
Peukert exponent (discharge efficiency). When unknown
it is recommended to keep this value at 1.25. A value of
1.00 disables the Peukert compensation. Call Customer
Service or your battery manufacturer before changing
this setting.
Default
Range
Step size
1.25
1.00 – 1.50
0.01