14 supply air blower performance (bp072, Belt drive) - side duct application – York BP 036 User Manual
Page 21

255027-YTG-B-0507
Unitary Products Group
21
TABLE 14: SUPPLY AIR BLOWER PERFORMANCE (BP072 BELT DRIVE) - SIDE DUCT APPLICATION
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP
1500
-
-
-
-
-
-
-
-
-
-
-
-
935
658
0.71 967
721
0.77 1001
786
0.84
1600
-
-
-
-
-
-
-
-
-
934
700
0.75 965
758
0.81 997
821
0.88 1031
886
0.95
1700
-
-
-
-
-
-
934
750
0.80 964
800
0.86 995
858
0.92 1028
921
0.99 1061
986
1.06
1800
-
-
-
936
810
0.87 964
849
0.91 994
899
0.96 1025
958
1.03 1058 1020
1.09 1091 1085
1.16
1900 939
885
0.95 966
910
0.98 994
949
1.02 1024 1000
1.07 1055 1058
1.13 1088 1121
1.20 1122 1185
1.27
2000 969
986
1.06 996
1011
1.08 1024 1050
1.13 1054 1100
1.18 1085 1159
1.24 1118 1222
1.31 1152 1286
1.38
2100 999
1088
1.17 1026 1113
1.19 1054 1152
1.24 1084 1202
1.29 1115 1261
1.35 1148 1324
1.42 1182 1388
1.49
2200 1028 1191
1.28 1055 1216
1.30 1084 1255
1.35 1114 1306
1.40 1145 1364
1.46 1178 1427
1.53 1211 1491
1.60
2300 1058 1296
1.39 1085 1321
1.42 1114 1360
1.46 1143 1410
1.51 1175 1468
1.57 1207 1531
1.64
-
-
-
2400 1087 1401
1.50 1114 1426
1.53 1143 1465
1.57 1173 1516
1.63 1204 1574
1.69
-
-
-
-
-
-
2500 1117 1509
1.62 1144 1533
1.65 1172 1573
1.69
-
-
-
-
-
-
-
-
-
-
-
-
2600 1146 1617
1.73
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2700
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2800
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
1
0.9
1.0
1.1
1.2
1.3
1.4
1.5
RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP
1500 1036
849
0.91 1072
908
0.97 1108
959
1.03 1146
999
1.07 1184 1026
1.10 1224 1035
1.11 1263 1024
1.10
1600 1066
949
1.02 1102 1008
1.08 1139 1059
1.14 1176 1099
1.18 1215 1126
1.21 1254 1135
1.22
-
-
-
1700 1096 1049
1.13 1132 1107
1.19 1169 1159
1.24 1206 1199
1.29 1245 1225
1.31
-
-
-
-
-
-
1800 1126 1148
1.23 1162 1207
1.30 1199 1258
1.35 1237 1298
1.39
-
-
-
-
-
-
-
-
-
1900 1156 1249
1.34 1192 1307
1.40 1229 1358
1.46
-
-
-
-
-
-
-
-
-
-
-
-
2000 1186 1350
1.45 1222 1408
1.51
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2100 1216 1452
1.56
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2200
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2300
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2400
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2600
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2700
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2800
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
Factory Installed AK56 blower sheave and A36 belt.