Ari/iso performance data – York YK145.00-EG4 User Manual
Page 7

Johnson Controls
7
Water Source Heat Pumps
Technical Guide: YK145.00-EG4 (309)
ARI/ISO PERFORMANCE DATA
PERFORMANCE DATA - ARI/ISO 13256-1 WATER LOOP CONDITIONS*
Unit Model
Flow Rate
(USGPM)
Air Flow
(SCFM)
Cooling
Capacity (Btuh)
EER
Heating
Capacity (Btuh)
COP
007
1.8
260
6,800
12.5
8,700
4.5
009
2.4
320
8,900
12.4
11,600
4.4
012
3.0
400
12,400
12.2
15,600
4.2
018
4.8
640
19,100
13.2
23,400
4.5
024
6.0
800
24,600
13.5
29,300
4.4
030
7.8
1000
29,800
13.3
35,300
4.5
036
9.0
1200
36,200
13.0
45,100
4.6
042
10.4
1400
42,700
12.7
50,600
4.4
048
12.0
1600
48,300
13.1
57,200
4.5
060
15.0
2000
60,500
13.4
70,800
4.6
070
17.5
2200
67,700
12.9
79,500
4.3
*Water Loop capacities are rated at 86°F EWT Cooling, 68°F EWT Heating.
PERFORMANCE DATA - ARI/ISO 13256-1 GROUND WATER CONDITIONS*
Unit Model
Flow Rate
(USGPM)
Air Flow
(SCFM)
Cooling
Capacity (Btuh)
EER
Heating
Capacity (Btuh)
COP
007
1.8
260
7,700
18.4
6,900
3.9
009
2.4
320
10,100
18.3
9,100
3.8
012
3.0
400
14,200
18.1
12,900
3.6
018
4.8
640
22,900
20.2
18,800
3.9
024
6.0
800
28,700
20.8
23,600
3.8
030
7.8
1000
33,600
20.0
29,100
3.8
036
9.0
1200
39,800
18.8
37,200
3.9
042
10.4
1400
45,800
19.1
42,300
3.9
048
12.0
1600
52,500
19.3
47,400
3.8
060
15.0
2000
66,400
19.8
59,000
4.0
070
17.5
2200
73,600
18.7
66,800
3.8
*Ground Water capacities are rated at 59°F EWT Cooling, 50°F EWT Heating.
PERFORMANCE DATA - ARI/ISO 13256-1 GROUND LOOP CONDITIONS*
Unit Model
Flow Rate
(USGPM)
Air Flow
(SCFM)
Cooling
Capacity (Btuh)
EER
Heating
Capacity (Btuh)
COP
007
1.8
260
7,100
14.6
5,500
3.4
009
2.4
320
9,300
14.5
6,900
3.3
012
3.0
400
13,000
14.3
10,200
3.1
018
4.8
640
20,600
15.7
13,900
3.4
024
6.0
800
26,400
16.1
17,400
3.3
030
7.8
1000
31,100
15.3
22,500
3.3
036
9.0
1200
37,500
14.8
28,600
3.3
042
10.4
1400
43,900
14.6
32,300
3.4
048
12.0
1600
49,800
15.0
37,800
3.3
060
15.0
2000
62,900
15.6
47,200
3.5
070
17.5
2200
70,100
14.7
52,400
3.3
*Ground Loop capacities are rated at 77°F EFT Cooling, 32°F EFT Heating.
NOTE:
1) All Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature.
2) All Heating capacities based upon 68°F DB, 59°F WB entering air temperature.