Physical data – York YK145.00-EG4 User Manual
Page 6
6
Johnson Controls
Technical Guide: YK145.00-EG4 (309)
Water Source Heat Pumps
PHYSICAL DATA
Model Series
007
009
012
018
024
030
036
042
048
060
070
Nominal Cooling (Ton)
1
0.5
0.75
1.0
1.5
2.0
2.5
3
3.5
4
5
6
Compressor-Type
Rotary
Reciprocating
Scroll
Air Coil-Type
Enhanced Copper tubes, Enhanced Aluminum Fins
Face Area(sq ft)
1.17
1.17
1.33
2.56
2.88
2.88
3.47
4.44
4.44
6.11
6.11
Rows/FPI
3/13
3/13
3/15
3/15
3/15
3/15
3/15
3/15
3/15
3/15
3/15
Water Coil-Type
Enhanced Surface Co-Axial
Water Connection (in)
1/2
1/2
1/2
3/4
3/4
3/4
3/4
3/4
3/4
1
1
Standard Blower/Motor
DWDI Forward-Curved Centrifugal / PSC Direct-Drive
Diameter x Width (in)
6x5
6x5
6x6
9x7
9x7
10x7T
10x7T
11x8T
11x8T 11x10T 11x10T
Motor HP
0.10/3
0.10/3
0.13/3
0.17/3
0.25/3
0.33/3
0.50/3
0.50/3
0.75/3
1.0/3
1.0/3
RSH Filter
Quantity-Size(in)
1-12x16 1-12x16 1-12x20 1-18x24 1-18x24 1-18x24 2-14x20 2-18x20 2-18x20 2-22x22 2-22x22
RSV Filter
Quantity-Size(in)
1-12x20 1-12x20 1-12x20 1-18x24 1-20x25 1-20x25 1-24x24 2-14x25 2-14x25 2-16x30 2-16x30
RSH Cabinet Weight (lb)
130
135
145
195
210
215
240
310
320
370
385
RSV Cabinet Weight (lb)
120
125
135
185
200
210
230
305
315
375
390
NOTE:
1) Nominal Capacity calculated in accordance with ARI / ISO Standard 13256-1 for Water Loop Application
OPERATING LIMITS*
COOLING
HEATING
Min. Entering Water
30°F
20°F
Max. Entering Water
110°F
90°F
*Units are capable of operation with an entering fluid temperature
range of 20°F to 110°F