York YCAL0080SC User Manual
Page 106

YORK INTERNATIONAL
106
PROBLEM
CAUSE
SOL
“LOW SUCTION PRESSURE”
4. TXV defective.
4. Replace TXV.
FAULT (CONT’D)
5. Reduced flow of chilled
5. Check GPM (See “Limitations”
liquid through the cooler.
in Installation section). Check
operation of pump, clean
pump strainer, purge chilled
liquid system of air.
6. Defective suction pressure
6. Replace transducer/low
transducer/low pressure
pressure switch or faulty
switch or wiring
wiring. Refer to “Service”
section for pressure/voltage
formula.
7. LLSV defective
7. Replace LLSV
“HIGH DISCHARGE
1. Condenser fans not operating
1. Check fan motor, fuses,
PRESSURE” FAULT
or operating backwards.
and contactors. Assure fan
blows air upward.
2. Too much refrigerant.
2. Remove refrigerant.
3. Air in refrigerant system.
3. Evacuate and recharge
system.
4. Defective discharge
4. Replace discharge pressure
pressure transducer.
transducer. Refer to Service
section for pressure/voltage
formula.
“LOW LIQUID TEMP”
1. Improperly adjusted leaving
1. Re-program the leaving
FAULT
chilled liquid temp cut-out
chilled liquid temp. cut-out.
(glycol only).
2. Micropanel setpoint/range
2. Re-adjust setpoint/range.
values improperly programmed.
3. Chilled liquid flow too low.
3. Increase chilled liquid flow –
refer to Limitations in Instal-
lation section.
4. Defective LWT or RWT sensor.
4. Compare sensor against a
(assure the sensor is properly
known good temperature
installed in the bottom of the well
sensing device. Refer to
with a generous amount of heat
Service section for temp/
conductive compound)
voltage table.
CONT’D
Service and Troubleshooting