Start tries, Start tries –34 – Xantrex Technology Automatic Generator User Manual
Page 82

Configuration
3–34
975-0082-01-01
Start Tries
“Start Tries” specifies how many times the Auto Gen Start will attempt to 
start the generator. On the first start try, the Auto Gen Start cranks the 
starter motor for the Crank Time. If the generator does not start, on 
subsequent start tries, the Auto Gen Start cranks the start motor for the 
Crank Retry Time.
When to use
This setting is automatically configured when you select a “Gen Type” for 
your generator. You should manually set “Start Tries” if you need to 
customize your Gen Type on the advice of your generator manufacturer or 
authorized service personnel.
Values
Default
1 to 10
3