York AHP18 THRU 60 User Manual
Page 3

255029-YTG-J-1007
Unitary Products Group
3
COOLING CAPACITY
Models
Rated CFM
Entering Air °F
(Dry / Wet Bulb)
MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG
35 / 61.5
40 / 68.5
45 / 76.0
50 / 84.0
FULL-CASED “A” TYPE MULTI-POSITION
AHP18B2A(N,H)21
650
85/72
24.5
22.3
19.9
17.3
80/67
22.6
20.3
18.0
15.6
75/62
18.5
16.4
14.2
12.0
70/57
15.0
13.1
10.9
8.5
AHP24B2A(N,H)21
800
85/72
35.0
31.8
28.4
24.7
80/67
32.2
29.1
25.7
22.3
75/62
26.4
23.4
21.0
17.1
70/57
21.4
18.6
20.2
12.1
AHP30B2A(N,H)21
1050
85/72
41.5
37.8
33.7
29.5
80/67
36.2
32.4
28.6
24.5
75/62
29.1
25.3
24.0
19.2
70/57
24.1
21.5
18.7
15.8
AHP36C2A(N,H)21
1200
85/72
51.3
46.7
41.7
36.8
80/67
41.1
36.3
31.8
27.1
75/62
32.1
27.0
29.4
21.9
70/57
27.6
25.4
23.5
18.3
AHP42C2C(N,H)21
1400
85/72
88.4
76.0
63.3
50.0
80/67
70.8
59.4
48.4
37.0
75/62
55.2
43.9
35.8
29.9
70/57
47.4
41.5
32.37
25.24
AHP48D2C(N,H)21
SHP48D2CN21
1600
85/72
100.5
86.4
72.0
56.8
80/67
80.4
67.5
55.0
42.1
75/62
62.7
49.9
40.7
34.0
70/57
53.9
47.2
36.81
28.71
AHP60D2C(N,H)21
SHP60D2CN21
1850
85/72
119.9
101.0
82.0
62.2
80/67
96.0
79.2
62.6
45.8
75/62
74.8
58.6
46.2
37.0
70/57
64.3
55.4
43.2
33.7