York AHP18 THRU 60 User Manual
Page 10
255029-YTG-J-1007
10
Unitary Products Group
2. Heaters are 3 Phase.
ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60
Models
Heat Kit -
Three Phase
Heater
Amps
240V
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75°C Wire Size - AWG
208V
240V
208V
240V
208V
240V
AHP24B**(N,H)21
4HK06501025
23.1
27.1
31.3
30
35
10
8
AHP30B**(N,H)21
4HK06501025
23.1
26.8
30.8
30
35
10
8
4HK065N1525
34.7
40.0
46.1
40
50
8
8
AHP36C**(N,H)21
4HK06501025
23.1
27.5
31.6
30
35
10
8
4HK06501525
34.7
40.0
46.1
40
50
8
8
AHP42C**(N,H)21
4HK06501025
23.1
29.1
33.4
30
35
10
8
4HK06501525
34.7
41.6
47.9
50
50
8
8
4HK06501825
41.4
48.9
56.3
50
60
8
6
AHP48D**(N,H)21
SHP48D**N21
4HK06501025
23.1
29.3
33.6
30
35
10
8
4HK06501525
34.7
41.8
48.1
50
50
8
8
4HK06501825
41.4
49.0
56.5
50
60
8
6
AHP60D**(N,H)21
SHP60D**N21
4HK06501025
23.1
34.5
38.4
35
40
8
8
4HK06501525
34.7
47.0
52.9
50
60
8
6
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60
Models
Heater
Model
Minimum Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75°C Wire Size - AWG
Circuit
1st
2nd
3rd
1st
2nd
3rd
1st
2nd
3rd
208/240
208/240
208/240 208/240 208/240 208/240 208/240 208/240 208/240
AHP60D**(N,H)21
SHP60D**N21
4HK16501825
31.9 / 35.4
22.4 / 25.9
- / -
35 / 40
25 / 30
- / -
8 / 8
10 / 10
- / -
4HK16502525
40.8 / 45.6
31.3 / 36.1
- / -
45 / 50
35 / 40
- / -
8 / 8
8 / 8
- / -
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.