Wiring diagrams – White Rodgers BLUE 2 1F89-0211 User Manual

Page 3

background image

3

WIRING DIAGRAMS

L

R

C

24 VAC

120 VAC

Hot

SYSTEM

MONITOR

SWITCH

Neutral

THERMOSTAT

SYSTEM

G

W2

Figure 2. Typical wiring diagram for single transformer systems

TRANSFORMER

(Class II Current Limited)

Changeover

Relay*

Y

O/B

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Aux/Emergency

Heat Relay

(Stage 2)

Fan

Relay

Optional

L

R

C

24 VAC

120 VAC

Hot

SYSTEM

MONITOR

SWITCH

Neutral

THERMOSTAT

SYSTEM

G

W2

Figure 3. Typical wiring diagram for two transformer systems with NO safety circuits

TRANSFORMER

(Class II Current Limited)

Changeover

Relay*

Y

O/B

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Aux/Emergency

Heat Relay

(Stage 2)

Fan

Relay

Optional

Limit or

Safety

Switches

TWO COMMONS MUST
BE JUMPERED TOGETHER!

HOT

NEUTRAL

120 VAC

24 VAC

CUT AND

TAPE OFF!

If safety circuits are in
only one of the systems,
remove the transformer
of the system with NO
safety circuits.

NOTE

L

R

C

SYSTEM

MONITOR

SWITCH

G

W2

Figure 4. Typical wiring diagram for two transformer systems with safety circuits in BOTH systems

Changeover

Relay*

Y

O/B

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Aux/Emergency

Heat Relay

(Stage 2)

Fan

Relay

Optional

TWO COMMONS MUST
BE JUMPERED TOGETHER!

24 VAC

120 VAC

HOT

NEUTRAL

THERMOSTAT

SYSTEM

HOT

NEUTRAL

120 VAC

Limit or

Safety

Switches

Limit or

Safety

Switches

Limit or

Safety

Switches

24 VAC

Limit or

Safety

Switches

COMMON

COMMON

Auxiliary

Heating

Transformer

(Class II

Current Limited)

Heat Pump Transformer

(Class II Current Limited)

24 VAC

ACCESSORY

RELAY N.O.

CONTACT

Polarity must be observed. If the HOT side of the
second transformer is jumpered to the COMMON side
of the first transformer a short will be made. Damage
to equipment will occur when power is restored.

NOTE

The accessory relay scheme
is required when safety
circuits exist in both systems.

NOTE