INSTALLER/CONFIGURATION MENU

1. This control can be configured for:

MS2 – Multi-Stage System (2 heat/2 cool)

HP1 – Heat Pump with one stage of compressor (2
heat/1 cool)

HP2 – Heat Pump with two stage compressor or two

compressor system, Gas or Electric backup; (Dual Fuel

see menu item 28) (4 heat/2 cool)

SS1 – Single Stage System (3 wire zone see wiring

diagrams.

2.

GAS or Electric (ELE) fan operation. If the heating
system requires the thermostat to energize the fan, select
ELE. Select GAS if the heating system energizes the
fan on a call for heat.

Note: Resetting the thermostat

switches the option to GAS.

3.

O/B Terminal selection – Selects the operation of the
reversing valve (when item 1 is set to HP1 or HP2 only).
When set to "O" the changeover valve will be energized
in COOL to accommodate the majority of heat applica-
tions. If the heat pump requires the changeover valve to
energize in HEAT, select "B".

4.

Programs per week – This control can be configured for
7 independent day or 5/1/1 day programming or nonpro-
grammable modes. Default is 7-day mode. The display
indicates

"7 Days" as default. Other options "5 Days" or

"0 Days" can be selected. If "0 Days" is selected for non-
programmable mode, the step for EMR will be skipped, as
this feature will not be available in this mode.

5.

Program Steps per day – This control can be configured
for 4 or 2 program steps per day. Default is

"4 PS" and

can be toggled between 4 PS and 2 PS.

6.

System Switch Configuration (MS2/SS1) – This ther-
mostat is configured for Heat and Cool with Auto change-
over default (Cool-Off-Heat-Auto). It can be configured as
Heat & Cool (Cool-Off-Heat), or Heat Only (Off-Heat), or
Cool Only (Cool-Off).

When the control is in heat pump configuration

(HP1/

HP2), the system switch configuration will have an

additional mode available namely,

Em for Emergency

Mode.

7.

Energy Management Recovery (EMR) – (this step is
skipped if configured as non-programmable). When set
to "On" causes the thermostat to start heating or cooling
early to make the building temperature reach the program
setpoint at the time you specify.

Example: The heating program is 65°F at night and 70°
at 7 AM. If the building temperature is 65°F, the difference
is 5°F. Allowing 5 minutes per °F rise, the thermostat set-
point will change to 70° at 6:35 AM. Cooling allows more
time per °F, because it takes longer to reach temperature.

8, 9 & 10.

Cycle Rate Selection – The factory default setting

is fast cycle (FA Cr) in all modes (Heat, Cool, Em). To
change to slow cycling (SL, Cr), press touch keys or

toggle between FA & SL. The cycle rates are below:

Mode

Fast rate

Slow rate

Heat

0.6°F

1.2°F

Cool

1.2°F

1.7°F

Em

1.2°F

1.7°F

11.

Select Compressor Lockout (CL) – Selecting (CL On)
will cause the thermostat to wait 5 minutes between cool-
ing cycles. This is intended to help protect the compressor
from short cycling. Some of the newer compressors have
a time delay built in and do not require this feature to be
activated in the thermostat. Your compressor manufactur-
er can tell you if this lockout feature is already present in
their system. When the thermostat compressor time delay
is activated, it will flash the set point for up to five minutes.

CONFIGURATION MENU

Menu

Reference

Number

Program-

mable

Non-Pro-

gram-

mable

Press

key

Displayed

Factory

(Default)

Press

or

to select from

listed options

Comments

29

(cont.)

29

(cont.)

26

(cont.)

dF (35)

5-50

Selects Dual Fuel setpoint (°F) with outdoor sensor available.

Cd (60)

0-99

Selects compressor delay in seconds.

30

30

27

AO (80)

35-74

Selects Auxiliary Heat cut out temperature. This item appears if HP1 or

HP2 is selected and outdoor sensor is installed and enabled.

31

31

28

bP (80)

79-20

Selects Blower balance point. Selection of 80 disables this feature. This

item appears if HP1 or HP2 is selected and outdoor sensor is installed

and enabled.

32

32

29

Hd (OFF)

On

Selects Humidity Display alternate with time.

33

33

30

Humidity

H1, OD

-20-20

-18

Selects Humidity Display adjustment.

34

34

31

HR (OFF)

LO, HI

Selects Auto Humidity reduction.

35

35

32

AH (OFF)

H, C, A

Selects Automatic Humidification.

36

36

33

CH (OFF)

On

Selects Cycle Humidifier.

37

37

34

OC (o)

od, OFF

Selects Optimum Comfort or Optimum Dehumidification.

38

38

35

Change UV

Lamp (OFF)

On

Selects Change UV Lamp feature.

350 Days

25-1975

Change UV Lamp duration days.

39

39

36

Change Pad

(OFF)

On

Selects Change Humidifier Pad feature.

1000 Hrs

25-1975

Change Humidifier Pad duration hours.

40

40

37

OFF

Change Filter

On

Selects Change Filter feature.

200 Hrs

25-1975

Change Filter duration hours.