BCP-3 Installation and Operation Manual

Button and Navigating Menus

The BCP-3 has three buttons.

The SET button function varies. When the Default Screen is
displayed, pressing the SET Button views the MENU. When
in the Menus and settings, the SET Button accepts the selected
entry or setting value.

When in the menus, pressing the Up and Down buttons will
scroll through the menu options. They can be used to change
the setting of a specific function. I.e., change the Set Point,
Differential, or System Trim. In addition, when in the default
screen, the Up and Down buttons will display the outdoor
temperature and Outdoor Cutoff.

At the end of every operation menu there is a

option

that allows the user to go back one menu level. If the SET
Button was held down for three seconds on the

option, the display will go back to the default screen.

SE

SE

T

T

DISPLAY UNIT:

F
C

SENSOR FAULT:
Output On
Output Off

CONTROL MODE:

Outdoor Reset
Set Point

OUTPUT MODE:
1-On/Off+1-Pump
1-On/Off+2-Pump
2-On/Off+1-Pump
1-Lo/Hi+1-Pump
3-On/Off

Startup Options

When the control is initiated for the first time or after a manual
reset, it will start its operation with the Startup Menu. Later, the
Startup menu can be accessed as an option from the operation
menu. An option must be accepted in each screen in the Startup
Menu to move to the next level.

Display Unit

Options: ºF, ºC

Default: ºF

SET

SET

//Display Unit

The BCP-3 will offer two different temperature display standards. If ºF is selected, all
temperatures will display in Fahrenheit. If ºC is selected, all temperatures will display in Celsius.

DISPLAY UNIT:

F
C

Control Mode

Options: Outdoor Reset, Set Point

Default: Outdoor Reset

SET

SET

//Display Unit/Control Mode

The new BCP-3 has two heating logics. Outdoor Reset; varies the system set point/target

based on outdoor temperature. This selection adds several menu options to adjust and fine tune
the reset curves: Reset Ratio, Offset, Min Water temp, Max Water temp, and Outdoor Cutoff. In
addition, a customized reset ratio curve will be available for specialized applications.

Set Point; gives the installer the flexibility of selecting a fixed set point. The Outdoor Cutoff will
be available if an outdoor sensor was installed.

CONTROL MODE:

Outdoor Reset
Set Point

Output Mode

Options: 1-On/Off+1-Pump, 1-On/Off+2-Pump, 2-On/Off+1-Pump, 3-On/Off

Default: 2-On/Off+1-Pump

SET

SET

//Display Unit/Control Mode/Output Mode

The new BCP-3 has multiple operating Output Modes of heating. Each can be applied based on
the number of boilers, stages, and pumps controlled. See Output Mode Table on page 4.

OUTPUT MODE:
1-On/Off+1-Pump
1-On/Off+2-Pump
2-On/Off+1-Pump
1-Lo/Hi+1-Pump
3-On/Off

Sensor Fault

Options: Output On, Output Off

Default: Output On

SET

SET

//..../Sensor Fault

The Sensor Fault will determine the operating status of the output relays when a sensor reads
Short or Open. On sensor fault, the Set Point will indicate

FAULT TGT=ON or OFF to

indicate the condition of the output and the faulty sensor will read

OPEN or SHORT to indicate

the condition of the sensor.

SENSOR FAULT:

Output On
Output Off