Bcp-3 installation and operation manual, Bcp-3 plumbing diagrams, Dhw pump y ellow w ires – Weil-McLain BCP-3 User Manual

Page 15: Blue w ires, White w ires, Output 1), Output 2), Output 3), Aquastat

background image

15

BCP-3 Installation and Operation Manual

Boiler1

DHW

Indirect

Building

Heat

System

Sensor

Outdoor

Sensor

T1

T2

COM

COM

T3+

T3-

EXT+

EXT

-

P+

P-

COM

24V

AC

}

System Sensor

}

Outdoor Sensor

}

DHW Call Dry Contact

}

Enable Dry Contact

}

Setback Dry Contact

Boiler

SYS

Pump

DHW
Pump

SET

SET

SYSTEM =

147F

TARGET =

150F

Y

ellow W

ires (Output 1)

Blue W

ires (Output 2)

Boiler2

Boiler3

System

Pump

White W

ires

(Output 3)

DHW

Pump

Boiler

DHW

Indirect

Building

Heat

System

Pump

System

Sensor

Outdoor

Sensor

T1

T2

COM

COM

T3+

T3-

EXT+

EXT

-

P+

P-

COM

24V

AC

}

System Sensor

}

Outdoor Sensor

}

DHW Call Dry Contact

}

Enable Dry Contact

}

Setback Dry Contact

Boiler

SYS

Pump

DHW
Pump

SET

SET

SYSTEM =

147F

TARGET =

150F

DHW Pump

Y

ellow W

ires

(Output 1)

Blue W

ires

(Output 2)

White W

ires

(Output 3)

Piping 1 On/Off Boiler +

System Pump + DHW Pump

Piping 3 On/Off Boilers

Aquastat

Aquastat

BCP-3

BCP-3

Output 1 Output 2 Output 3

Output 1 Output 2 Output 3

BCP-3 Plumbing Diagrams

NOTES:

The BCP-3 does not source any output power to any of its
relays. A power source must supply pumps with power and
the control can break the hot leg.

Weil McLain recommends using a separate power source
to the control from any pumps, boilers, heavy electric
equipment.

When wiring a sensor to the BCP-3, connect the Shield to
the COM terminal on the BCP-3 end. DO NOT connect
the Shield at the sensor end.

• Weil McLain is aware that each installation is unique.

Thus, any wiring or piping diagrams in this document
are to represent control operation concept only.