5

BCP-3 Installation and Operation Manual

Output Mode Table

Output Mode

Description

Output 1

(Yellow

Wires)

Output 2

(Blue

Wires)

Output 3

(White
Wires)

Notes

1-On/Off+1-Pump

One On/Off boiler and a System pump

Sys Pump

Boiler

Not used

1-On/Off+2-Pump

One On/Off boiler, a System pump and

a Domestic Hot Water Pump

Sys Pump

Boiler

DHW

Pump

2-On/Off+1-Pump Two On/Off boilers and a System pump Sys Pump

Boiler 1

Boiler 2

DHW Pump

controlled by DHW

Aquastat

1-Lo/Hi+1-Pump

One Lo/Hi boiler and a System pump

Sys Pump

Boiler Lo

Boiler Hi

DHW Pump

controlled by DHW

Aquastat

3-On/Off

Three On/Off boilers and NO pumps

Boiler 1

Boiler 2

Boiler 3

Sys Pump controlled

using other controls

or run constantly.

Wiring the Boiler Output

Single-Stage (On/Off) Boiler Wiring

If any of the "1-On/Off" Output Modes is selected, wire the two Blue wires to the boiler circuit.

If more than one On/Off boiler is to be controlled by the BCP-3, follow the wiring colors as per
the Output Mode Table above.

The BCP-3 does not source any output power to the boiler. The relay makes when energized.

Two-Stage (Lo/Hi) Boiler wiring

Wire the two Blue wires to the boiler control circuit initiating the Low Fire signal.

Then, wire the two White wires to the High fire circuit.

The BCP-3 does not source any output power to the boiler. The relay makes when energized.

Wiring the System and DHW Pump Outputs

System Pump Wiring (Not Available With "3-On/Off" Output Mode)

The BCP-3 will control the System Pump relay (Maximum of 1/8 HP) in all Output Modes
except (3-On/Off), as all outputs will be used by boiler stages. In this scenario, the system pump
can be controlled independently using a switch or left to run constantly.

Wire the two Yellow wires to the System Pump circuit.

The BCP-3 does not source any output power to the pump. The relay makes when energized to
switch the power to the pump on.

DHW Pump Wiring (Available Only With "1-On/Off+2-Pumps" Output Mode)

The BCP-3 will control the DHW Pump relay (Maximum of 1/8 HP) only in (1-On/Off+2-Pump)
Output Mode. In the other modes, the DHW pump can be controlled using an external DHW
aquastat.

If the BCP-3 is controlling the DHW pump, wire the two White wires to the DHW Pump circuit.

The BCP-3 does not source any output power to the pump. The relay makes when energized to
switch the power to the pump on.

On/Off Boiler

Output Wiring

Blue

YELLOW

System Pump
Output Wiring

L

N

120VAC

Two-Stage Boiler

Output Wiring

Blue (Lo Fire)

White (Hi Fire)

WHITE

DHW Pump

Output Wiring

L

N

120VAC